NTI E-1W Environment Monitoring System with 1-Wire Sensor Interface

NTI

$200.00
Part Number:
E-1W
UPC:
796168570539
Availability:
Usually ships the same day
1:
Monitor and manage environmental and security conditions over IP
2:
2 digital inputs sensitive to contact closure
3:
Free 15-Day Trial (See below FAQ)
4:
2-Year NTI Warranty
ADD OPTIONS:
NTI E-1W Environment Monitoring System with 1-Wire Sensor Interface

NTI E-1W Environment Monitoring System with 1-Wire Sensor Interface monitors critical environmental conditions, such as temperature, humidity, liquid water presence, power, intrusion, and smoke. When a sensor goes out of range of a configurable threshold, the system will notify you via email, web page, network management (SNMP), and/or SMS messages (via email-to-SMS).

The system supports 24 single reading 1-wire sensors in any combination - temperature, humidity, dew point, thermocouple or digital inputs - and 2 separate digital inputs. It functions independently or as an IP-connected remote sensor for the E-2D/5D/16D.

NTI E-1W Environment Monitoring System with 1-Wire Sensor Interface Features:

  • Monitor and manage environmental and security conditions over IP.
  • Sensors supported:
    • 2 digital inputs sensitive to contact closure.
    • 2 RJ11 6P4C connectors for daisy-chaining 1-wire temperature/humidity/dew point, thermocouple, or digital input expanders in any combination.
      • Up to 24 temperature, thermocouple, or any single reading 1-wire sensor can be connected between both RJ11 connectors.
      • Up to 8 temperature/humidity/dew point combination 1-wire sensors can be connected between both RJ11 connectors. Each temperature/humidity/dew point sensor is equivalent to 3 single reading sensors.
      • Up to 12 E-DI2-1W digital input expanders can be connected between both RJ11 connectors to allow a maximum of 24 additional digital inputs. Each E-DI2-1W is equivalent to 2 single reading sensors.
      • Maximum cable length supported on each connector is up to 600ft (183 m) depending on the configuration and number of connected sensors.
      • Use RJ11 splitters (RJ11-3JCK) to daisy-chain 1-wire sensors (sold separately).
  • Sensors are hot pluggable.
    • The sensors will automatically be detected on power up or a Detect Devices button on the summary page can be selected when logged into the unit.
  • Monitors (ping) up to 4 IP network devices - alerts are sent if devices are not responding.
  • Sensor conditions can be configured to trigger alerts by themselves, and/or be used in combination with other alerts to trigger one Smart Alert.
  • Supports 4 IP network video cameras for live view of any facility.
  • Create multiple alerts for any installed sensor.
  • Sensor conditions can be configured to trigger alerts by themselves, and/or be used in combination with other alerts to trigger one Smart Alert.
    • Configure up to 32 alerts, and one Smart Alert.
  • Dual redundant power supplies for connection to two separate power sources.
    • The second power supply is sold separately.
  • Available with optional Power over Ethernet (POE).
  • Integrates with various Open Source SNMP monitoring packages Nagios
    • The unit can be polled via SNMP.
  • Optional intuitive graphical management software provides an easy-to-use, unified interface for both monitoring and configuring up to 3,000 ENVIROMUX units and all connected sensors.
  • Security: HTTPS, SSLv3, AES 256-bit encryption, 16-character username/password authentication, user account restricted access rights.
  • Ideal for a wide range of applications including IT infrastructure monitoring, cold storage/freezer monitoring, or any unmanned area that needs to be monitored.

Why not buy this NTI E-1W Environment Monitoring System with 1-Wire Sensor Interface today?

NTI E-1W Environment Monitoring System with 1-Wire Sensor Interface Specification:

RJ11 Sensor Ports
      • Two RJ11 6P4C jacks for daisy-chaining 1-wire temperature/humidity/dew point, thermocouple, or digital input expanders in any combination.
        • Up to 24 temperature, thermocouple, or any single reading 1-wire sensor can be split between both RJ11 connectors.
        • Up to 8 temperature/humidity/dew point combination 1-wire sensors can be split between both RJ11 connectors. Each temperature/humidity/dew point sensor is equivalent to 3 single reading sensors
        • Up to 12 digital input expanders can be split between both RJ11 connectors to allow a maximum of 24 additional digital inputs. Each digital input expander is equivalent to 2 single reading sensors
        • Maximum cable length supported on each connector is up to 600ft (183 m) depending on the configuration and number of connected sensors.
          • This maximum includes the cable length of each sensor.
        • RJ11 splitters or t-tap boards (RJ11-3JCK) for convenient daisy-chaining are sold separately.
Dry Contact Closures
      • Two screw terminal pairs for connecting dry contact devices and liquid detection sensors.
USB Port
      • One female Micro USB connector - reserved for future use.
Ethernet Port
      • One female RJ45 connector.
      • 10/100 Base-T Ethernet interface.
Protocols
      • HTTP/HTTPS, SNMP V1/V2c, SMTP, TCP/IP, Syslog, SNTP, DHCP, SSLv3, AES 256-bit, 3DES, Blowfish, RSA, EDH-RSA, Arcfour
        • SSLv3 has been disabled in the following browser versions and affects HTTPS connection to the E-1W:
          • Microsoft Edge
          • Firefox Version 34 and newer
          • Opera Version 25 and newer
          • Google Chrome Version 40 and newer
          • Internet Explorer and Safari: all versions allow SSLv3, if there are connection issues check if SSLv3 is manually disabled.
      • Compatible with any SNMP management software.
        • The unit can be polled via SNMP.
      • Operates and configures via HTTP/HTTPS web page.
      • An IP address can be assigned to the E-1W automatically by a DHCP server.
      • Generates SNMP traps, email alerts, syslog messages, and SMS messages (via email-to-SMS).
        • Alerts are posted in event log, which is accessible through Web user interface.
        • Email alerts can be sent to 9 addresses.
          • Users can configure the schedule for when they will be alerted.
          • Email alerts are not compatible with TLS.
Dimensions
      • WxDxH in: 4x3.65x1.37 (102x93x35 mm).
Power
      • E-1W:
        • Dual DC power provides dual redundancy.
          • If the first power source fails, the unit will automatically, without interruption, switch over to the second power source.
          • The unit draws power from the source with the highest DC voltage (nominal 5.5V).
          • If both sources have exactly the same voltage, it will draw in part from each of them.
        • 110 to 240 VAC at 50 or 60 Hz via AC adapter.
          • Includes one country-specific AC adapter. The second AC adapter is sold separately (PWR-SPLY-ELC).
        • Input voltage: 5.5VDC ±5%
      • E-1WP:
        • Built-in Power over Ethernet and dual DC power provides triple redundancy.
          • Power over Ethernet standards supported: IEEE 802.3af, 802.3at.
            • Proprietary schemes such as Cisco Discovery Protocol are not supported.
              • Similar legacy switches and routers will have to use PWR-SPLY-ELC.
        • If the first power source fails, the unit will automatically, without interruption, switch over to the second power source.
        • The unit draws power from the source with the highest DC voltage (nominal 5.5V).
        • If two or more sources have exactly the same voltage, it will draw in part from each of them.
      • 110 to 240 VAC at 50 or 60 Hz via AC adapter (not included).
        • Country-specific AC adapters sold separately (PWR-SPLY-ELC).
      • Input voltage: 5.5VDC ±5%
MTBF
      • E-1W: 703,871 hours
Environmental
      • Operating & Storage Temperature: -4 to 167˚F (-20 to 75˚C).
      • Operating & Storage Relative Humidity: 0 to 90% non-condensing RH.
Regulatory Approvals
      • CE, RoHS.
Warranty
    • Two years.

Frequently Asked Questions